Page 215 - CITS - Electrician - Trade Practical
P. 215

ELECTRICIAN - CITS




           TASK 5 : Testing of transformer after winding

           1  Test the primary and secondary windings for continuity with a megger.
           2  Measure and record the primary and secondary winding resistance in Table 6.
                                                         Table 6
                                             Transformer winding resistance

                                           Primary              resistance.............ohm
                                           Secondary 1 resistance..................ohm
                                           Secondary 2 resistance..................ohm
                                           Secondary 3 resistance..................ohm
           3  Measure and record the insulation resistance, between windings and frame in Table7.
                                                         Table 7

                                              Insulation resistance between
                                       Primary & secondary windings...............megohm

                                       Secondary windings...............................megohm
                                       (in case of seperate windings)
                                       Windings and frame..............................megohm


           4  Connect the primary winding of the transformer with the rated voltage. Keeping the secondary open, test the
              primary and the secondary voltage. Record the finding in Table 8

                                                         Table 8
                                                  No-load measurement

                                            Primary voltage........................volt
                                            Secondary voltage
                                                 1 .............................volt
                                                 2 .............................volt

                                                 3 .............................volt

           5  Observe for vibration sound of the core. If it is abnormal, tighten the stampings, also check for tightness of the
              coil.
           6  Connect the transformer with suiTable load so that full load current passes through the secondary, and record
              the voltage and current at load in Table 9.
                                                         Table 9
                                                   Load measurement
                                              Primary voltage..................volt
                                              Primary current..................amp

                                              Secondaryvoltage..............volt
                                              Primary current..................amp


           7  Keep the transformer on full load for eight hours continously. Observe the change  in temperature of the
              winding and core by touching. If the temperature raise is within the class of insulation, the transformer is O.K.







                                                           198

                                     CITS : Power - Electrician & Wireman - Exercise 86