Page 95 - CITS - Electrician - Trade Practical
P. 95

ELECTRICIAN - CITS



           EXERCISE 39 : To measure and improve the Power factor

                                      of AC circuit

            Objectives

           At the end of this exercise you shall be able to:
           •  identify the power factor meter, check its terminals, scale, rating and connection
           •  connect the inductive & resistive loads in AC circuit and measure the power factor
           •  connect the required value of capacitors to improve the power factor in AC circuits.

           Requirements

           Tools/Equipments/Instruments
           •  Combination Plier 165mm,        insulated        •  Resistive (lamp) load
              -1 No.                                              1 Ph. 230V, 5KW               -1 No.
           •  Screw Driver 150mm,         -1 No.               •  Inductive load (Ind. Motors,
           •  Neon Tester 75mm, 500 V    -1 No.                   choke) 1 Phase, 230 V         -1 No.
           •  Electrician knife insulated      -1 No.          Materials/Components
           •  Voltmeter MC, 300 V            -1 No.            •  PVC copper wire 1.5 sq.mm     -2 meter.
           •  Ammeter MI, 10 A               -1 No.            •  Static capacitors 2.5 µf
           •  1 Ph. Power factor meter,             A n a l o g   400 V,5 µf 400 V              -Each 4 Nos.
              10 A, 230 V                    -1 No.            •  Test lamp 100 W, 230V         -1 No.
           •  Multi meter Digital, 3  digit        -1 No.      •  DPST switch 16 A, 230 V       -1 No.
                                1/2

            Procedure

           TASK 1 : Identify the resistive & inductive loads & PF meters
           1  Draw the neat circuit diagram of measurement of power factor in 1 Ph. AC resistive load, Inductive load and
              capacitive load.
           2  Check & study the Power factor meter- check the terminals, scale, rating & connection.
           3  Collect the different static capacitors and check their values
           4  Calculate the VAR / KVAR value of capacitors required to improve the power factor of AC circuit.


           TASK 2 : Connect and measure the power factor in AC resistive & inductive circuits
           1  Make the circuit connection of resistive load as per circuit diagram.
           2  Check the circuit and connect to 1 Ph. AC supply through DPST switch.

           3  Switch ON the supply, check the power factor meter reading and record in tabular column
           4  Switch OFF the supply and make the circuit connection of inductive load as per circuit diagram.
           5  Switch ON the supply, check the power factor meter reading and record in tabular column.
           6  Switch OFF the supply, and connect one static capacitor in parallel with inductive load.
           7  Switch ON the supply and check the change in power factor meter reading & record the same.

           8  Connect multiple No. of capacitors until the power factor improves to 1 (unity).
           9  Check the ammeter reading for decrease in current when power factor value comes to 1 (unity).
           10 Switch OFF the supply and disconnect the circuit.