Page 127 - Electrician - TT (Volume 1)
P. 127

ELECTRICIAN - CITS






           Voltage operated ELCB
           This device is used for making and breaking a circuit.  It automatically trips or breaks the circuit when the potential
           difference between the protected metal work of the nstallation and the general mass of earth exceeds 24V.  This
           voltage signal will cause the relay to operate (Fig 1).
           Voltage operated ELCBs are meant to be used where it is not practicable to meet the requirements of IEE  wiring
           regulation by direct earthing or where additional protection is desirable.

           Current operated ELCB:  This  device  is  used  for  making  and  breaking  a  circuit  and  for  breaking  a  circuit
           automatically when the vector sum of current in all conductors differs from zero by a predetermined amount.
           Current operated ELCBs are much more reliable in operation, easier to install and maintain.
           Construction of  current operated ELCB: It consists of a Torroid ring made of high permeability magnetic
           material.    It  has  two  primary  windings  each  carrying  the  current  flowing  through  phase  and  neutral  of  the
           installation.  The secondary winding is connected to a highly sensitive electro - magnetic trip relay which operates
           the trip mechanism.

           Working principle
           The residual current device (RCD) is a circuit breaker which continuously compares the current in the phase with
           that in the neutral. The difference between the two is called as the residual current which is flowing to earth.
           The purpose of the residual current device is to monitor the residual current and to switch off the circuit if it rises
           from a preset level (Fig 2&3).


               Fig 1                                                 Fig 2
















               Fig 3














           The main contacts are closed against the pressure of a spring which, provides the energy to open them when the
           device trips.  Phase and neutral current pass through identical coils wound in opposing direction on a magnetic
           circuit, so that each coil will provide equal but opposing numbers of ampere turns when there is no residual
           current.  The opposing ampere turns will cancel and no magnetic flux will be set up in the magnetic circuit.
           In a healthy circuit the sum of the current in phases is equal to the current in the neutral and vector sum of all
           the current is equal to zero.  If there is any insulation fault in the circuit then leakage current flows to earth.  This
           residual current passes to the circuit through the phase coil but returns through the earth path and avoids the
           neutral coil, which will therefore carry less current.





                                                           114

                                    CITS : Power - Electrician & Wireman - Lesson 20-25
   122   123   124   125   126   127   128   129   130   131   132