Page 189 - Electrician - TT (Volume 1)
P. 189

ELECTRICIAN - CITS




           Effect of load pf on wattmeter reading

           Power factor from two wattmeter reading
              tan¢=√3 (W1-W2)
              (W1+W2)
              ¢=tan~√3 (W1-W2)


            Phase-sequence indicator (Meter)

           Objectives: At the end of this lesson you shall be able to
           •  describe the method of finding the phase sequence of a 3-phase supply using a phase-sequence indicator
           •  explain the methods of finding phase sequence using lamps.



           Phase sequence
           A three-phase alternator contains three sets of coils positioned 120° apart and its output is a three-phase voltage
           as shown in Fig 1. A three-phase voltage consists of three voltage waves, 120 electrical degrees apart.
           At a time 0, phase U is passing through zero volts with positively increasing voltage. (Fig 1)  V follows with its zero
           crossing 1/3 of the period later and the same applies to W with respect to V. The order in which the three-phases
           attain their maximum or minimum values is called the phase sequence. In the illustration given here the phase
           sequence is U,V,W.
           Importance of correct  phase sequence: Correct phase sequence is important in the construction and connection
           of various three-phase systems. For example, correct phase sequence is important when the outputs of three-
           phase alternators must be paralleled into a common voltage system. The phase `U’ of one alternator must be
           connected to phase `U’ of another alternator. The phase `V’ to phase `V’ and phase `W’ to phase `W’ must be
           similarly connected to each other.
           In the case of an induction motor, reversal of the sequence results in the reversal of the direction of motor rotation
           which will drive the machinery the wrong way.
           Phase-sequence  indicator(meter): A  phase-sequence  indicator  (meter)  provides  a  means  of  ensuring  the
           correct phase-sequence of a three-phase system. The phase-sequence indicator consists of 3 terminals `UVW’
           to which three-phases of the supply are connected. When the supply is fed to the indicator a disc in the indicator
           moves either in the clockwise direction or in the anticlockwise direction. The direction of the disc movement is
           marked with an arrowhead on the indicator. Below the arrowhead the correct sequence is marked. (Fig 2)

             Fig 1                                              Fig 2





























                                                           176
                                    CITS : Power - Electrician & Wireman - Lesson 26-29
   184   185   186   187   188   189   190   191   192   193   194