Page 130 - CITS - Electrician - Trade Practical
P. 130

ELECTRICIAN - CITS


           EXERCISE 55 : To connect single & twin tube light fitting


            Objectives

           At the end of this exercise you shall be able to:
           •  identify the parts of fluorescent tube light fitting
           •  test the ballast, starter, capacitor and tube light
           •  make the connection of single & twin tube light and test.

           Requirements

           Tools/Equipments/Instruments
           •  Combination Plier 165mm,                         •  Tube light fitting- single & twin
              insulated                     - 1 No.               With choke, starter, capacitor
           •  Screw Driver 150mm,                                 4’ 40 watts, 230 V          - 1 No. each
              insulated stem                - 1 No.            Materials/Components
           •  Connector screw driver 150mm,
              insulated stem                - 1 No.            •  PVC copper wire 1.0 sq.mm        - 2 m
           •  Neon Tester 75mm, 500 V       - 1 No.            •  Hook up wire Single strand       - 2 m
           •  Electrician knife Insulated    - 1 No.           •  Test lamp 100 W, 230V            - 1 No.
           •  Multi meter Digital, 3  digit   - 1 No.          •  Fluorescent tube light 4’ 40 W, 230 V - 3 Nos.
                                1/2
                                                               •  Insulation tape PVC, 19mm        - 1 role


            Procedure


           TASK 1:Testing of ballast starter and tubelight
           1  Draw the circuit diagram of single tube light connection.
           2  Take the single tube light fitting and identify the ballast, starter, capacitor and side holders.
           3  Test the ballast by connecting it to the supply in series with test lamp.

                       Observation: 1. The lamp should glow dim for good condition.
                                             2. If lamp glows bright OR does not glow, ballast is defective.
           4  Test the starter by connecting it to the supply in series with test lamp.
                        Observation: 1. The lamp should glow with flickering for good condition.
                                              2. If lamp glows constantly OR does not glow, starter is defective.
           5  Make the connections of single fluorescent tube light as per circuit diagram.

           6  Check the connections and connect to 1 ph. AC supply, observe the intensity of light.
           7  Switch OFF the supply and disconnect the fluorescent lamp.

           TASK 2: Connecting & Testing of twin fluorescent lamp fitting
           1  Draw the circuit diagram of twin tube light connection.
           2  Take the twin tube light fitting and identify the ballast, starter, capacitor and side holders.
               (Twin tube light fitting has each 2 No’s of ballast, starter, capacitor and tube light)

           3  Test the ballast and starter before making connections.
           4  Make the connections of twin fluorescent tube light as per circuit diagram.
           5  Check the connections and connect to 1 ph. AC supply, observe the light intensity of both tubes.
           6  Switch OFF the supply and disconnect the fluorescent lamp.