Page 265 - CITS - Electrician - Trade Practical
P. 265

ELECTRICIAN - CITS


            Procedure

           TASK 1 :
           1  Design the circuit as per required logic.

           2  Draw the circuit   diagram.
           3  Prepare the wiring Table.
              Note : Use standard symbols while preparing the power and control circuit, the design should meet
              all the requirements.


           TASK 2 :

           1  Remove the detachable plate from the control panel.

           2  Place the accessories on the plate as per layout.
              Note  :  Ensure  sufficient  spacing  between  components  while  preparing  layout.  The  minimum
              spacing between components and race ways should be 100 mm for 415 V and 50 to 75 mm for less
              than 415 V system
           3  Fix the accessories on the plate by making necessary marking, drilling and tapping.

              Note : Make sure that the marking is correct and use only suiTable size drill bit and tap


           TASK 3 :

           1  Take the measurement of control and power cable as per lay out.
           2  Cut the required length of control and power cable.
           3  Insert identification ferrule in each end of wire as per wiring diagram and wiring Table.


              Note : Insert all the strand of the  cable in the copper lug while crimping
           1  Lay the cable through the slotted wire duct and dress it properly.
           2  Refit the detachable plate to the control panel.
           3  Bunch the control cables up to the push buttons and indication lamps which are fixed in panel door using nylon
              cable tie.
           4  Strip the insulation and crimp the copper lug on each end of wire using crimping tool.

              Note : Remove only sufficient length of cable insulation and use proper sized lugs
           5  Connect the cable to the accessories as per diagram.
              Note : Over tightening of screw have to be avoided otherwise this can crush the strand and give a
              poor contact
           6  Connect suiTable size of earth wire to the cabinet and door.
           7  Connect 3 phase supply with neutral to the control panel.
           8  Check the circuit and test the DOL starter.

              RESULT
              Wired up and tested the DOL starter.