           TASK 2: Estimate the cost / bill of materials for wiring of industrial installation / workshop










































              The main switch, motor switch and starters are assumed to be mounted at a height of 1.5m from
              the ground level.
              Height of horizontal run from the ground level will be 2.5m
              The cost of motors and starters are not included in the estimate

              SL.       Motor        FL current IL(A)    Starting current       Recommended Cable size
              No.                                           I8=2IL(A)
                                                                           2.0 Sq mm copper conductor cable
               1      5HP Motor            7.5                 15          (17A) or 2.5Sq mm Aluminium
                                                                           Conductor Cable (16)A
                                                                           2.0Sq mm Copper conductor cable
               2      3 HP Motor          4.68                9.36
                                                                           (17A)
                                                                           1.0Sq mm Copper conductor cable
               3     1/2 HP Motor         2.25                 4.5
                                                                           (11A) Minimum recommended Cable
                                                                           1.0Sq mm Copper conductor cable
               4      1 HP Motor          1.56                3.12
                                                                           (11A) Minimum recommended Cable
           Select the suiTable switches and distribution board
           •  32 A,415V ICTP switch with fuse cab be used as main switch
           •  16A, 415V ICTP switches with fuses can be used form 5HP , 3HP , & 1HP motors
           •  16 A , 240V ICDP Switches with fuses can be used for ½ HP motor
           •  415V, 4 Way,16A per way ic distribution board with Natural link can be used for power distribution.
           Draw the single line diagram of power wiring
           Calculate the size and length of conduit.