Page 46 - CITS - Electrician - Trade Practical
P. 46

v

                                                                                   ELECTRICIAN - CITS



           EXERCISE 16 : Grouping of Cells



           Objectives

           At the end of this exercise you shall be able to
           •  identify the different types of primary cells and measure the EMF
           •  make the series & parallel connection of cells
           •  check the voltage & current in series and parallel connection of cells
           •   calculate internal resistance of cell.

           Requirements


           Tools/Equipments/Instruments                        •  DC Voltmeter (0-15 V)          - 1 No.
           •  Combination plier (165mm, insulated)  - 1 No.    •  DC milli Ammeter (500 mA)      - 1 No.
           •  Connector screw driver (100mm)    - 1 No.        Materials/Components
           •  Wire stripper (100mm)             - 1 No.
           •  Digital Multi meter (3 digit)      - 1 No.       •  Connecting wire (1.0 sq.mm)    - As reqd.
                                1/2
                                                                                                 - 8 No’s.
                                                               •  Primary cells (1.5 V)
           •  Variable resistance (0-10 Ω)      - 1 No.        •  Cell holder                    - 1 No.
            Procedure

           TASK 1: Connect the cells in series and test the voltage & current
           1  Draw the circuit diagram of series / parallel connection of cells.

           2  Connect the cells in series as per circuit diagram.
           3  Close the switch and measure the total voltage and current in the circuit.
           4  Measure the voltage drop and calculate internal resistance in the cells.
           5  Note down the measured values and record in tabular column.




           TASK 2: Connect the cells in parallel and test the voltage & current
           1  Connect the cells in parallel as per circuit diagram.
           2  Close the switch and measure the total voltage and current in the circuit.
           3  Measure the voltage drop and calculate internal resistance in the cells.
           4  Note down the measured values and record in tabular column.

           5  Compare and differentiate between series & parallel connection of cells.
           Safety precautions
           •  Use proper and insulated tools.
           •  Connect the cells with proper polarity.

           •  Take the meter readings correctly.
           •  Do not short the terminals of cells













                                                           29