Page 183 - Electrician - TT (Volume 1)
P. 183

ELECTRICIAN - CITS




           Fig 2  shows this phasor addition for a situation where the loads are balanced and the currents are equal. The
           result is that  the current in the neutral line I  is zero.
                                                 N
           Therefore, for a balanced load the neutral conductor carries no current.
           Earthing  of  neutral conductor:  Supply  of  electrical  energy  to  commercial  and  domestic  consumers  is  an
           important application of three-phase electricity. For `low voltage distribution’ - in the simplest case, i.e. supply of
           light and power to buildings - there are two requirements.

           1  It is desirable to use conductors operating at the highest possible voltage but with low current in order to save
              on expensive conductor material.
           2  For safety reasons, the voltage between the conductor and earth must not exceed 250V.

           A voltage distribution system according to criterion 2, only  possible with a low line voltage  below 250 V. However,
           this is contrary to criterion 1. On the other hand, with a star connection, a line voltage of 415V is available. In this
           case, there is only 240V between the supply line and the neutral conductor. Criterion 1 is satisfied and, to comply
           with 2, the neutral conductor is earthed.
           Indian  Electricity  Rules: I.E.Rules insist that the neutral conductor must be earthed by two separate and
           distinct connections to earth. Rule No.61(1)(a), Rule No.67(1)(a) and Rule No.32 insist on the identification of
           neutral at the point of commencement of supply at the consumer’s premises, and also prevent the use of cut outs
           or links in the neutral conductor. BIS stipulate the method of earthing the neutral. (Code No.17.4 of IS 3043-1966)
           Cross-sectional area of neutral conductor: The neutral conductor in a 3-phase, 4-wire system should have a
           smaller cross-section. (half of the cross-section of the supply lines).


              Fig 1                                              Fig 2















           Two phase system

           Two electrically insulated windings are placed 90 degree electrical apart in a uniform magnetic field.
           If the windings are rotated with constant angular velocity, the EMF generated will have a phase difference of 90
           degree.




























                                                           170
                                    CITS : Power - Electrician & Wireman - Lesson 26-29
   178   179   180   181   182   183   184   185   186   187   188