Page 336 - CITS - Electrician - Trade Practical
P. 336

ELECTRICIAN - CITS




           3  Locate the fixed main contact and movable main contacts.
           4  Check the continuity of the contacts.
           5  Locate the tripping coil terminals.
           6  Remove the arcing chamber unit and test the arc chutes and diverters.
           7  Locate the manual tripping lever to trip manually.
           8  Connect the ACB to the main supply and switch ON.

           9  Check the condition of indicating and tripping lamps.
           10 Charge the breaker manually by operating handle.
           11 Check the engaged main contact and confirm by checking its continuity.
           12 Press the manual tripping switch and confirm its disengagement of the contacts.

           13 Charge again the breaker and confirm the engagement of the main contacts.
           14 Switch ‘OFF’ the AC mains, the arcing chamber and close the removed covers.
           15 Submit the reports to your Instructor and get it approved.
                                                         Table 2

                         Sl. No     Parts no          Name of the part         Function

                         1

                         2

                         3
                         4

                         5

                         6

                         7

                         8

                         9

                         10

                         11
























                                                           319

                                    CITS : Power - Electrician & Wireman - Exercise 114
   331   332   333   334   335   336   337   338   339   340   341