              Note: Now the fault current set value is 2 Amp and the relay should trip in the time as per the dial
              indication.

           7  Switch ‘ON’ the current injection and note down the tripping indicated by the timer fitted on the current injection
              unit.

           8  Reduce the time by setting TMS by 0.5
              Note: Since the short circuit current cannot be generated practically the tripping time is reduced by
              taking the short circuit current is present now.
           9  Ensure the rotating aluminium disc returns to its original position.

           10 Switch ON the injection unit and note down the tripping time in seconds.
              Note: This time will be half time of the first reading.
           11 Change the tap setting at 2 amps slot in the relay and repeat the steps 4 to 9.

           12 Record the readings in the Table and get it approved by your instructor.
                                                         Table 1
                                     Test tripping of circuit breaker definite time charts

            Sl. No   Tap setting     TMS value   Time      Multiplier    Total fault   Actual     Error in %
                     current                                             current      tripping
                                                                                      current
            1

            2

            3


            4


           TASK 2 : Tripping circuit breaker in extreme inverse characteristic condition

           1  Repeat the step 1 to 3 in Task 1.
           2  Set the TMS at 0.2 position.
           3  Set the tap setting plug into maximum current input on the dial.
           4  Select the maximum multiplier value in the dial record the fault current (plug set value ‘X’ multiplier) and the
              tripping time in Table 2.
           5  Check the pickup current for the tap set value.
           6  Set the fault current in the current injector unit
           7  Switch ‘ON’ and note down the actual tripping time in Table 2.

           8  Try to some higher value of fault current and repeat the step 5 to 7. Record the values in Table 2.
                                                         Table 2
            Sl. No  Tap setting     TMS value    Time     Multiplier    Total fault   Actual      Error in %
                    current                                             current      tripping
                                                                                     current
            1
            2

            3
            4




                                                           321

                                    CITS : Power - Electrician & Wireman - Exercise 115