           EXERCISE 115 :  Test tripping characteristic of circuit

                                       breaker for over current and short circuit
                                       current


           Objectives

           At the end of this exercise you shall be able to
           •  connect relay and circuit breaker for test tripping
           •  set the current injection unit for tripping current
           •  set the tripping current for definite time lag (over current)
           •  set the current for extreme inverse characteristic (short circuit current).
           Requirements

           Tools/Equipments/Instruments
           •   Trainees tool kit                - 1 No.
           •   Air circuit breaker 400 KA 415V
              with manual                       - 1 No.
           •   Over current relay with manual   - 1 No.
           •   Current injection unit with manual   - 1 No.

           Procedure

           TASK 1 : Tripping of circuit breaker for definite time with set fault current
              This exercise is prepared to set the relay in definite time tripping in over current conditions and
              extreme inverse tripping in short circuit situations. This model relay is not having the facility of
              various tripping characteristics.
              However short circuit current situation can be provided to trip the relay in short time by setting time
              Multiplier Setting (TMS) to trip the relay instantly at high fault current situation.
           1   Connect the relay, circuit breaker with the current injection unit by referring  in block diagram. (Fig 1)




















           2  Check all the connections as per the instruction manual.
           3  Set the tap setting current in 1 amp and note down the multiplier, time in seconds in Table 1.

           4  Set the TMS at position 1 marked in the dial.
           5  Check the pick up current of the set value of tap setting current and note down values in Table 1.
           6  Set the fault current by selecting multiplier from the dial and note corresponding time in seconds and note the
              values in Table 1.