Page 141 - Electrician - TT (Volume 1)
P. 141

ELECTRICIAN - CITS




           Electrodes shall, as far as practicable, be embedded in earth below the permanent moisture level.
           The length of the rod and pipe electrodes shall not be less than 2.5 m.
           Except where rock is encountered, pipes and rods shall be driven to a depth of atleast 2.5 m. The length of the
           electrodes shall be atleast 2.5 m, and the inclination not more than 300 from the vertical.
           Plate electrodes (Fig 5): Plate electrodes,when made of galvanised iron or steel,shall not be less than 6.3 mm
           in thickness. Plate electrodes of copper shall be not less than 3.15 mm in thickness. Plate electrodes shall be of
           a size, at least 60 cm by 60 cm.

              Fig 5




































           Plate electrodes shall be buried such that the top edge is at a depth not less than 1.5 m from the surface of the
           ground.
           Where the resistance of one plate electrode is higher than the required value, two or more plates shall be used in
           parallel. In such a case, the two plates shall be separated from each other by not less than 8.0 m.
           Plates shall preferably be set vertically.
           Plate electrodes is recommended in generating stations and substations.
           If  necessary,  plate  electrodes  shall  have  a  galvanized  iron  water  pipe  buried  vertically  and  adjacent  to  the
           electrode. One end of the pipe shall be atleast 5 cm above the surface of the ground, and it need not be more
           than 10 cm. The internal diameter of the pipe shall be atleast 5 cm and need not be more than 10 cm. The length
           of pipe, if under the earth’s surface, shall be such that it should be able to reach the centre of the plate. In no case,
           however, shall it be more than the depth of the bottom edge of the plate.
           Methods of reducing the resistance of an earth electrode to an acceptable value:

           The earth electrode resistance is found higher in rocky or sandy areas where moisture is very low.
           The following methods are suggested to bring down the earth electrode resistance to an acceptable value.
           1  After installing the rod or pipe or plate in earth, the earth pit ( the area surrounding the rod / pipe / plate) should
              be treated with layers of coke and common salt to get a lower value of earth resistance.

           2  Pouring water in the earth pit at repeated intervals lowers the earth electrode resistance.





                                                           128

                                    CITS : Power - Electrician & Wireman - Lesson 20-25                                                                  CITS : Power - Electrician & Wireman - Lesson 20-25
   136   137   138   139   140   141   142   143   144   145   146