Page 137 - Electrician - TT (Volume 1)
P. 137

ELECTRICIAN - CITS






           where              I is the line current
                              R  is the  resistance  of one core only.
           The above points could be explained through the following set of examples.
           Example 1
           A guest house installation has   the following  loads  connected  to the  three phase  415  V  supply with  neutral.
           Select a  proper size   of   cable   for    this installation.
           1  Lighting - 3 circuits of tungsten lighting total 2860 watts
           2  Power from 3 x 30A ring circuits to 16A socket outlets for
              a  1 x 7 KW Water heater (Instant)

              b  2 x 3 KW Immersion heater (Thermostatically controlled)
              c  Cooking  appliances: 1 x 3 KW cooker
                                                      1 x 10.7 KW cooker
           Current demand in amperes in each of the circuit is calculated by referring the Table 1. Calculate  current  taking
           account into the   diversity factor.
           Assuming  the declared  voltage as 240 volts and the length  of the longest run in a circuit as 50 metres
           Permissible voltage drop at the rate of 3%






              If  the size of the conductor  selected is  35.0 sq.mm which can  carry 69 amps, the voltage drop at
              69 amperes  rating will be 1 volt for every 7.2 metres cable run.

           For  50  metres cable  run  the voltage drop at 69 amps current rating = 50 / 7.2 volts.
           Voltage drop for 65 amps
           As  the actual voltage drop  in the   circuit,  that  is   6.54 volts,   is  well  within   the permissible value, of  7.2 volts,
           the cable  selected  is suitable for the installation.
             SI. No      Demand           Current Demand          Diversity Factor    Current allowing for for
                        description           (Ampere)               (Table 2)         (Ampere)
               1      Lighting          11.9                  75%                     9.00

               2     Power  i           30                    100%                    30
                                 ii     30                     80%                    24        72.00
                                 iii    30                     60%                    18

               3     Water heaters (inst)  29.2               100%                    29.2

               4     Water heaters      25.00                 100%                    25.00
                     (thermo)

               5     Cooker i           12.5                  80%                     10.00
                                  ii    44.5                  100%                     44.5


             Total current    = 213.1
            Total current demand (allowing diversity) = 189.7 amps
            Load  spread  over 3 phases = 189.7/3 = 63.23  amps, say 65  amps  per phase.





                                                           124

                                    CITS : Power - Electrician & Wireman - Lesson 20-25
   132   133   134   135   136   137   138   139   140   141   142