Page 255 - Electrician - TT (Volume 1)
P. 255

ELECTRICIAN - CITS




           Parallel operation of two single phase transformers


           Objectives: At the end of this lesson you shall be able to:
           •  state the necessity  of parallel operation of transformers
           •  state the conditions to be full filled for the parallel operation of transformers
           •  explain how to determine the polarity terminals of transformer.


           Necessity of parallel operation of transformers
           1  When the power demand of the load increases, two or more transformer may be operated in parallel.
           2  When the power demand decreases, only required numbers of transformer may be operated with their full load
              capacity. Where as the remaining transformers may be switched "OFF" and taken for general maintenance/
              service.

           3  Thus the efficiencies and life of the transformers increases and the losses are reduced.
           4  It provides more reliability of power i.e., even one transformer fails or become out of service, other transformers
              will supply to the certain amount of load.
           5  It is not economical to manufacture a single very large capacity transformer. Thus operationg two or more
              numbers of optimal capacity transformers in parallel is more economical.
           6  It is easy to plan the maintenance schedule of the transforemers, hence the cost of maintenance and spares
              are reduced.
           Conditions
           1  the same voltage ratio
           2  Input voltage must be same
           3  the same per unit (or percentage) impedance

           4  the same polarity
           5  the same phase sequence and zero relative phase displacement, for  3 phase transformers.
           Of these (4) and (5) are absolutely essential (1) and (2) must be satisfied to a close degree.
           There is more allowance for a wide extent with (3), but the more nearly it is true, the better will be the load division
           between several transformers.
           Parallel operation
           Fig 1 shows two single phase transformers connected in parallel with their primary windings connected to the
           same supply and their secondary windings supplying a common load.
           When operating two or more transformers in parallel, to have satisfactory performance the following conditions
           should be met

           Voltage ratio: If voltage readings on the open secondaries of various transformers, to be run in parallel, do
           not show identical values, there will be circulating currents between the secondaries (and therefore between
           primaries also) when the secondary terminals are connected in parallel.  The impedances of transformers is
           small, so that a small percentage voltage difference may be sufficient to circulate considerable current and cause
           additional I2R loss.
           When secondaries are loaded, the circulating current will tend to produce unequal loading conditions.  Thus it
           may be impossible to take the full load output from the parallel connected group without one of the transformers
           becoming excessively heated.
           Impedance: The currents carried by the two transformers are proportional to their ratings:
           •  if their numerical or ohmic impedances are inversely proportional to those ratings, and
           •  their per unit impedances are identical.





                                                           242
                                    CITS : Power - Electrician & Wireman - Lesson 41-49
   250   251   252   253   254   255   256   257   258   259   260