Page 259 - Electrician - TT (Volume 1)
P. 259

ELECTRICIAN - CITS





           The primary and secondary line voltages and line currents are out of phase with each other by 30o. The ratio of
           secondary to primary voltage  3  is  times the transformation ratio of each transformer.


             Fig 3                                            Fig 4































           Parallel operation of 3-phase transformer

           Objectives: At the end of this lesson you shall be able to:
           •  explain parallel opration
           •  states the conditions for parallel operation of 3 phase transformer
           •  states the necessity of parallel opertion.


           Parallel operation
           Operating two or more transformers by connecting  their primaries  in parallel  to a common supply line and
           connecting their respective secondaries in parallel with a common load-busbars  is called as parallel operaion of
           transformers.
           Conditions for pararllel opertion of transformers:

           When operating two or more transformer in parallel, the following conditions have to be satisfied for the best
           performance of the transformer.
           1  The voltage ratio must be same.

           2  The per unit impedance  or percentage  impedance  should be same i.e., the ratio between  the equivalent
              leakage reactance and the equivalent resistance(X/R)should be same.
           3  The polarities must be same.
           4  For three phase transformers

              i   The phase sequence must be same
              ii   The vector group must be same (i.e., The relative phase displacement between the secondary line voltages
                must be zero)







                                                           246
                                    CITS : Power - Electrician & Wireman - Lesson 41-49
   254   255   256   257   258   259   260   261   262   263   264