Page 133 - Electrician - TT (Volume 2)
P. 133

ELECTRICIAN - CITS





















           For insulation resistance test

           Between windings: As shown in Fig 4, one end of the Megger lead is connected to any one terminal of the RYB
           and the other is connected to F1 or F2 of the field winding. If  the Megger reads one megohm or more, then the
           insulation resistance is accepted as okay.

           If there is short, between the armature and field windings, the Megger reads zero ohms. If it is weak, it shows
           less than one megohm.
           Testing insulation resistance between body and windings: As shown in Fig 5, one lead of the Megger is
           connected to one of the leads of the RYB, and the other lead of the Megger is connected to the body. If the
           insulation between the windings and the frame is all right, the Megger reads more than one megohm.



















           The field is tested by connecting one terminal of the Megger to F1 or F2 of the field and the other terminal to the
           body as shown in Fig 6. If the insulation  between the field and the frame is all right, the Megger reads more than
           one megohm. A lower reading than one megohm shows weak insulation and leakage to the ground.




















           Caution
           While conducting the insulation resistance test, if the Megger reads zero, then it should be concluded that the
           insulation of the  winding has failed completely and needs thorough checking.
              The permissible insulation resistance should not be less than 1 megohm.



                                                           120

                                   CITS : Power - Electrician & Wireman - Lesson 76-85                                                                     CITS : Power - Electrician & Wireman - Lesson 76-85
   128   129   130   131   132   133   134   135   136   137   138