Page 162 - Electrician - TT (Volume 2)
P. 162

ELECTRICIAN - CITS





                Fig 9                                        Fig 10















            Testing of armature winding


           Objectives: At the end of this lesson you shall be able to:
           •  describe the methods of testing armature, such as the
              – winding resistance test
              – insulation resistance test
              – growler test
              – voltage drop test..



           Testing the winding : After an armature is wound and the leads are connected to the commutator, a test should
           be conducted. From this test, defects may be revealed, which might have occurred during winding. The common
           defects in armature windings are grounding, shorts in the coils, open in the coil and reversal in the coil connection.
           These defects can be located by different test procedures.

           Armature winding resistance test : Resistance of the armature coil is measured by using a low range  ohmmeter
           and  preferably  with  the  Kelvin  bridge. Resistance  between consecutive segments in the case of simplex lap
           winding (for wave and multiplex windings at a distance of commutator pitch Yc) is measured. Fig 1 shows a
           simple arrangement to measure the resistance between the  successive  commutator  segments.
           As  shown  in Fig 1, a  cotton tape with a counterweight is passed around the commutator to hold the connecting
           leads to the segments. Measurement of resistance is done in all the coils by  changing  the  position  of the
           connecting leads to successive commutator segments. The resistance measured should be the same in all coils.
           Lower resistance shows short in turns, while a higher resistance shows higher numbers of turns or open in the
           coil.

           Insulation  resistance test :  With  a bare copper wire short all the commutator segments.  (Fig 2)  Test  the
           insulation resistance between the body and the commutator segments by a 500V Megger, for armatures rated up
           to 250 volts. The IR so measured shall be greater than 1 megohm. If the value is less than 1 megohm, moisture
           in the winding or a weak insulation is  to be suspected.

               Fig 1                                             Fig 2






















 148                                                       149

                                    CITS : Power - Electrician & Wireman - Lesson 86-92
   157   158   159   160   161   162   163   164   165   166   167