Page 169 - Electrician - TT (Volume 2)
P. 169

ELECTRICIAN - CITS




           Wire sizes and turns
           Primary - 3187 turns of size 0.16 mm or 37 SWG
           Secondary - 88 turns of size 1.00 mm or 19 SWG
           Stampings:  Considering the thickness of each stamping as 0.35 mm, for the total thickness of 21 mm we may
           require 60 stampings. Considering the space between stampings and the stacking we may require 55 stampings
           only. Hence EI 60/21 type 55 numbers of stampings having  0.35 mm thickness are to be procured.
           Testing of transformer after rewinding:  After rewinding the core assembly, the transformer is to be inspected
           for proper tightness of the core and coil as well as proper termination of the end leads.
           Insulation resistance test : Insulation resistance is measured between windings and core with a 500 volts
           Megger. The reading so obtained shall be infinity and in no case below one megohm.
           Transformation ratio test: Keeping the transformer secondary open, the primary shall be connected to the rated
           AC voltage. With the help of suitable voltmeters both the primary and secondary voltage shall be measured.
           Load test : The transformer shall be connected with a suitable load, so that the full load secondary current flows
           through  the secondary of the transformer winding. The raise in the winding temperature shall be observed  by a
           suitable industrial thermometer, on the load.
           The transformer temperature will raise initially and after some time the temperature will come to a standstill. This
           raise in temperature shall be noted and it shall be within the limit of class of insulation of the transformer designed.
           Short circuit test  :   Where it is not possible  to load  the transformer directly, the secondary  winding  of the
           transformer shall be short circuited and the low voltage on the primary shall be adjusted through a dimmerstat
           so that full load secondary current flows through the secondary winding of the transformer. The transformer so
           switched on shall be tested for raise in temperature to ascertain the class of insulation.
              Generally oil-cooled  transformers are of class-A where-as air-cooled transformers may be class

                                                         Table 1

                                                Standard size of stampings
                   Specification
                   of stampings   a    b      c       d     e        f     g     i     k1     k2     k3
                   EI42          42    28     7       3.5   21       14    28    35    3.5    —      24.5
                   EI48          48    52     8       3.5   24       16    32    40    4      —      28
                   EI54          54    36     9       3.5   27       18    36    45    4.5    —      31.5

                   EI60          60    40     10      3.5   30       20    40    50    5      —      35
                   EI66          66    44     11      4.5   33       22    44    55    5.5    —      38.5
                   EI78          78    52     13      4.5   39       26    52    65    6.5    —      45.5
                   EI84          84    56     14      4.5   42       28    56    70    7      —      49

                   EI92          92    62.3   11.3    4.5   51       23    69    82    5      6.5    57.5
                   EI106         106   70.5   14.5    5.5   56       29    77    94    6      8.5    64.5
                   EI130         130   87.5   17.5    6.8   70       35    95    115   7.5    10     80
                   EI150         150   100    20      7.8   80       40    110   135   7.5    12.5   92.5
                   EI170         170   117.5  22.5    8     95       45    125  150    10     12.5   107.5

                   EI195         195   134.5  25.5    9.5   109      51    144  171    12     13.5   122.5
                   EI231         231   166    29      10    137      58    173  204    13.5   15.5   152.5

              Nominal thickness of stampings:0.35 mm and 0.5 mm. ‘A’ or ‘E’.





                                                           156                                                                                                                    PB

                                    CITS : Power - Electrician & Wireman - Lesson 86-92
   164   165   166   167   168   169   170   171   172   173   174