Page 238 - Electrician - TT (Volume 2)
P. 238

ELECTRICIAN - CITS




           To mount the contactor on rail first place the back top groove on the top of rail and turn it downwards against the
           lower rail which will cause the spring of the contactor to retract and snap into place behind the rail. There is a slot
           in the spring clip of the contactor so that the clip can be retracted using small screw driver or connector to remove
           the contactor if required. To avoid fouling the underneath of the accessories use screws with low profile heads.
           The contactor arrangements and terminals are usually labeled which conforms to BS 5583. For example 1 and 2
           for NC contacts, 3 and 4 for NO contacts, odd numbers like 1, 3 and 5 for incoming terminals and even numbers
           like 2, 4 and  6 for outgoing terminals of the main contacts of contactors and OLR.

           The conductor should be trimmed off to that the conductor does not insert more than the half way through the
           connectors. Single strand wire should be folded back to give additional thickness. The over tightening of screw
           have to be avoided otherwise this can crush the strand  and give a weak connection.

           All the internal wiring should be terminated in the top and external wiring in the bottom of the connectors to avoid
           the crossover of both wirings. Flexible conduit and cables have to be installed in such a way that the liquid or
           water if any can drain away from the fitting and grommets.
           An earth terminal usually green or green yellow to be clamped to the rail and ensure the cabinet and door are
           earthed properly.

           An insulated separator can be used to isolate the high voltage connections from others. End stops are used to
           clamps the connectors together and close the open terminals on one end, sometimes the earth terminal will do
           the same job as in Fig 5.
           The control panel should be grounded properly so that control panel should have proper earthing bolts / nuts.  If
           more ground points are used a common earth plate should be fixed inside the cabinet as in Fig 5.
           U loops of the cables as long as possible facing down and anchored on each side of the hinged doors and panel
           with screws or bolts and do not use adhesive. Place the sleeve and spiral flexible conduits of suitable size over
           the cables running between the hinged doors and panel as in Fig 6.
           The care to be given to the bundle of wires which is mounted on the hinged doors should not restrict the opening
           and closing of the door or the doors should not damage the wires.
           Minimize the use of cable ties if the raceways are used.  They may be cut off during troubleshooting and rarely
           replaced.


                Fig 5                                              Fig 6


























           Routing and bunching
           Routing : Conductors and cables should run from terminal to terminal without any intervening joins and cross over.
           Extra length should be left at connector / terminals where assembly needs to be disconnected for maintenance and
           servicing. Multi core cable terminations have to be adequately supported to avoid undue strain on the terminals.





                                                           225

 CITS : Power - Electrician & Wireman - Lesson 93-100  CITS : Power - Electrician & Wireman - Lesson 93-100
   233   234   235   236   237   238   239   240   241   242   243