Page 338 - Electrician - TT (Volume 2)
P. 338

ELECTRICIAN - CITS




           14 Energy storage handle

           15 Draw out /in hole
           16 Rocker repository
           17 Trip reset button
           Internal construction of air circuit breaker

           The internal parts of an ACB in Fig.2
           1  Sheet steel supporting structure
           2  Current transformer for protection trip unit
           3  Pole group insulating box
           4  Horizontal rare terminals

           5  Plate for fixed main contacts
           6  Plates for fixed arcing contacts
           7  Plate for main moving contacts
           8  Plates for moving arcing contacts
           9  Arcing chamber

           10 Terminal box for fixed version - sliding contacts for withdrawable version
           11 Protection trip unit
           12 Circuit breaker closing and opening control
           13 Closing springs
           14 Spring loading arrangement

           15 Manual releasing lever
           Principle of operation of air circuit breaker
           •  When the circuit breaker opens the circuit either under the normal condition or in the fault condition, some Arc
              is produced between the main contacts and some current flows to the load, called transition current through
              the arc.
           •  This Arc and the current should be suppressed /eliminated especially during the fault condition otherwise the
              severity of  the fault level will be more and damages the circuit which leads to the electric fire.
           •  During the period of Arc some voltage appears across the main contacts called transition voltage, which will
              be more than the rated system / supply voltage.
           •  To quench  the Arc, this transition voltage should be reduced or the Arc voltage to be increased. The minimum
              voltage required to maintain the arc is called as Arc voltage. In ACB, the Arc voltage is increased in the
              following three ways.
           •  Arc voltage can be increased  by cooling arc plasma by air.   The temperature of arc plasma  is reduced, more
              voltage  will be required to maintain the arc.

           •  By splitting the arc into a number of series in Arc chute will increases the arc voltage.
           •  Arc voltage can be increased by lengthening the arc path. As length of arc path is increased its resistance of
              the arc path will increase  hence the  arc voltage is increased.
           Some ACB contains two pairs of contact . The main pair carries the current and the  made of copper. An additional
           pair of contact (Arc contact) is made of carbon. When the breaker is opened, the main contact opens first. and  the
           arc contact remains in touch.  The arcing gets initiated when arc  contacts are separated.
           Hence transition voltage will be reduced.





                                                           325

 CITS : Power - Electrician & Wireman - Lesson 106-116  CITS : Power - Electrician & Wireman - Lesson 106-116
   333   334   335   336   337   338   339   340   341   342   343