Page 321 - CITS - Electrician - Trade Practical
P. 321

ELECTRICIAN - CITS





              Fig 3                                         Fig 4




















           TASK 4: Fasten the jumper in pin insulator
           1  Keep the ladder on the pole and ask the helper to hold the ladder. climb up the ladder with the guide rope and
              spanner set.

           2  Fix the pin type insulator to the cross-arm of the existing pole.
           3  Tape the neck of the pin insulator with flat aluminium tape.
           4  Lift the Aluminium Conductor Steel Reinforced (ACSR) conductor and keep it in between pole and the pin
              insulator.

           5  Lay the ACSR wire on the slot of the pin insulator and ask the other helper to stretch the conductor with a wire
              stripper.
           6  Take the binding wire of about 2 metres length, leaving equal length on both sides. Bind two turns on the
              insulation (Fig 1a) around the neck of the pin insulator.
           7  Make a knot of the binding wire with the free ends tightly. (Fig 1b)
           8  Bind the free ends of the binding conductor over the line conductor tightly in the opposite direction. (Fig 2)









































                                                           304

                                    CITS : Power - Electrician & Wireman - Exercise 110
   316   317   318   319   320   321   322   323   324   325   326