           TASK 4: End termination of XLPE cable
           1  Prepare the cable and cut the exceeding length
           2  Remove the outer sheath for the length “L” (“L” see the Table).
           3  Abrade the outer sheath for 100 mm and clean with solvent.


























           4  Remove the copper tape screen leaving 25 mm out of the outer sheath.










           5  Remove the semi-conductive layer leaving 15 mm out of the copper tape screen taking care not to damage
              the insulation.







           6  Bare the conductor for the length “C” (“C”= inside depth of lug) for bolted lug or “C+5mm” in case of compression
              lug.







           7  Position the lug and crimp it






           8  Apply a layer of red mastic tape (20% overlap) on the outer sheath for 30 mm.