            4                                                            Termination joint














           TASK 3: Join 11 kV XLPE cable
           1  Identify the accessories

              •  Crimping type jointing ferrule.
              •  Self amalgamating insulating tapes.
              •  Self amalgamating semiconducting tapes.

              •  Non-linear stress grading pads.
              •  Earthing connector and clamps.
              •  Plastic mould and jointing compound etc.
           2  Cut the given cable to half, Strip the outer sheath, armour and inner sheath, insulation screen, core insulation
              and conductor screen.
           3  Joint all the conductor cores shall be joint with the help of jointing ferrule and its crimping by suiTable crimping
              tool.

           4  Fill up the space between the ferrule and the core insulation and the crimped portion in ferrule with semi
              conducting tape, so that it forms a smooth and round profile with 2 mm. Overlap on the insulation on each side
              of the ferrule as shown in Figure given below.








           5  Apply stress grading pad of 30mm on both sides of the semiconducting for a distance of 20 mm tape.