           The secondary of a current transformer should never be left open under any circumstances.

           Potential transformers (Fig 12)

              Fig 12

















           PT  are used to  measure HV  in combination with low voltage voltmeters. They  are accurate-ratio step-down
           transformers. When divided  by voltage transformation ratio, gives the true voltage on the high voltage side.
           Shell-type ordinary two-winding transformers discussed. Power rating is extremely small. Upto voltages of 5,000
           usually of the dry type 5,000 to 13,800 volts, either dry type or oil immersed type.
           Voltages above 13,800 always oil immersed type.Operate instruments or relays or pilot lights, their ratings are
           usually of 40 to 100 W. For safety, the secondary should be completely insulated from the high-voltage primary
           and grounded. (Fig 13)

            Fig 13



















           Power measurement (Fig 14)


             Fig 14
























                                                           256
                                    CITS : Power - Electrician & Wireman - Lesson 41-49