           Star delta (Y D) connection (Fig 7)
           This connection is used at the end of the transmission linewhere the voltage is to be stepped down. The primary
           winding is Y-connected with grounded neutral. The ratio between the secondary and primary line voltage is 1/3
           times the transformation ratio of each transformer. There is a 30° shift between the primary and secondary line
           voltages .A Y D transformer bank cannot be paralleled with either a Y Y bank. Also, third harmonic currents flows
           in the D to provide a sinusoidal flux.
           Delta star  (D Y) connection (Fig 8)

           At the beginning of high transmission system.
           The neutral of the secondary is grounded for providing 3-phase 4-wire service.
           Can be used to serve both the 3-phase power equipment and single-phase lighting circuits.
           Primary and secondary line voltages and line currents are out of phase with each other by 30°.
           Impossible to parallel such a bank with DD or Y Y bank of transformers even though the voltage ratios are correctly
           adjusted.