Page 384 - Electronic Mechanic - TP - Volume - 2
P. 384
ELECTRONICS MECHANIC - CITS
Step Description Remarks
6 Configure necessary digital input signals by The factory settings are:
setting the following parameters: • p29301[2]: 1 (SON)
• p29301[2]: DI1
• p29302[2]: 2 (RESET)
• p29302[2]: DI2
• p29303[2]: 3 (CWL)
• p29303[2]: DI3 • p29304[2]: 4 (CCWL)
• p29304[2]: DI4
• p29305[2]: 12 (CWE)
• p29305[2]: DI5
• p29306[2]: 13 (CCWE)
• p29306[2]: DI6 • p29307[2]: 15 (SPD1)
• p29307[2]: DI7
• p29308[2]: 16 (SPD2)
• p29308[2]: DI8
Refer to "Digital inputs/outputs (DIs/DOs) (Page 61)".
7 Configure speed setpoint. You can select the external analog speed setpoint or
one of seven fixed speed setpoints by configuring the
digital signals SPD3, SPD2 and SPD1.
SPD3 : SPD2 : SPD1
0 : 0 : 0: external analog speed setpoint (analog input
1)
0 : 0 : 1: fixed speed setpoint 1 (p1001)
0 : 1 : 0: fixed speed setpoint 2 (p1002)
0 : 1 : 1: fixed speed setpoint 3 (p1003)
1 : 0 : 0: fixed speed setpoint 4 (p1004)
1 : 0 : 1: fixed speed setpoint 5 (p1005)
1 : 1 : 0: fixed speed setpoint 6 (p1006)
1 : 1 : 1: fixed speed setpoint 7 (p1007)
Refer to "Configuring speed setpoint (Page 162)".
8 If the external analog speed setpoint is used,
configure the maximum analog speed setpoint
corresponding to 10 V by setting parameter
p29060.
9 Clear faults and alarms. Refer to "Diagnostics (Page 249)".
10 Change SON status to be high level (1) and The actual speed of the servo motor can be viewed
the servo motor starts running according to from the BOP operating display.
configured speed setpoint. The default display is the actual speed. Refer to "Actual
status display (Page 112)".
11 The system commissioning in speed control You can check the system performance. If it is not ok,
mode ends. you can adjust it. Refer to "Tuning (Page 195)".
367