Page 228 - Electrician - TT (Volume 2)
P. 228

ELECTRICIAN - CITS





              When the no-volt coil is activated by the start button, the auxiliary contact of the starter should
              close to complete the NVC circuit and should remain in the closed position even after the start
              button is released.
           If the overload relay is not functioning properly i.e. not tripping the motor as per setting of the current rating, then
           replace it with a new one as per with the original specification of the manufacturer.

           If a humming and chattering noise is observed in the starter then check for the rated voltage. If the voltage is okay,
           then check for any gummy material adhered to the pole faces. If found, clean it properly. See whether the shading
           ring over the pole faces of the NVC is loose. Tighten it properly and also check the spring tension of NVC housing.

           Suppose the starter trips often then, check up the load on the motor. (Might be due to overload or over tension
           of the belt) Reduce the load or tension of the belt. Further check up the motor current in each phase. If the motor
           takes higher current than specified even though the load is normal, then the fault is with the motor and not with
           the starter. After attending to the faults and rectifying them, reassemble the starter, connect it to the motor for
           proper functioning.
           Starter check - chart given below could be used to locate trouble in a D.O.L. starter.

                                               Maintenance of DOL starters
                 Trouble                     Cause                                 Remedy
             I  Starter check chart
             1  Contacts chatter    Low voltage, coil is not picking up    Correct the voltage condition. In case there is
                                    properly.                        persistent low voltage,
                                    Broken pole shading ring.        check the supply of the transformer tapping.
                                    Poor contact between the pole      Replace.
                                    faces of the magnet.             Clean the pole faces.
                                    Poor contact between fixed and      Clean contacts and adjust, if necessary.
                                    movable contacts.
             2  Welding or          Low voltage preventing magnet    Correct the voltage condition. In case of
                overheating.        from sealing.                  persistent low voltage, which is accepted normal
                                    Abnormal in rush current.      change the NVC to lower voltage coil. Check
                                    Short circuit in the motor.    excessive load current or use larger contactor.
                                    Foreign matter preventing      Remove the fault and check to ensure that the
                                    contacts from closing.         fuse rating is correct. Clean contacts with
                                    Rapid inching.                 suitable solvent. Install larger device or caution
                                                                   the  operator not to operate the inch button too
                                                                   quickly.
             3  Short life of contact    Weak contact pressure.    Adjust or replace contact springs.
                 points
             4  Noisy magnets       Broken shading coil.           Replace magnet.
                                    Magnet faces not mating.       Align or replace magnet assembly.
                                    Dirt or rust on magnet faces.   Clean with suitable solvents.

             5  Failure to pick up    Low voltage.                 Check system voltage. In case persistent low
                 and seal the contacts.                            voltage, change to a lower voltage coil.
                                    Coil open or short-circuited.    Replace the coil.
                                    Mechanical obstruction for the    Clean and check for free movement of
                                    moving parts.                  contact assembly.
             6  Failure of moving    Voltage not removed.          Check wiring in the NVC coil circuit.
                 mechanism to       Worn or rusted parts causing    Replace parts.
                 drop out.          binding. Residual magnetism due   Replace worn out magnet parts
                                    to lack of air gap in magnet path.  or demagnetise the parts.
                                    Gummy substance on pole faces   Clean with suitable solvent.
                                    causing binding.






                                                           215

 CITS : Power - Electrician & Wireman - Lesson 93-100  CITS : Power - Electrician & Wireman - Lesson 93-100
   223   224   225   226   227   228   229   230   231   232   233