Note:
- When inverter is not running, the display alternates between the values for “Not Running”
and “Running”.
- Per default, the setpoint and actual frequency values are displayed alternately.
P0007 Backlight delay time Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 0
P-Group: FUNC Active: first confirm QuickComm: No Max: 2000
Defines time period after which the backlight display turns off if no operator keys have been pressed.
Value:
P0007 = 0:
Backlight always on (default state).
P0007 = 1 - 2000:
Number of seconds after which the backlight will turn off.
P0010 Commissioning parameter Min: 0
CStat: CT Datatype: U16 Unit: - Def: 0
P-Group: ALWAYS Active: first confirm QuickComm: No Max: 30
Filters parameters so that only those related to a particular functional group are selected.
Possible Settings:
0 Ready
1 Quick commissioning
2 Inverter
29 Download
30 Factory setting
Dependency:
- Reset to 0 for inverter to run.
- P0003 (user access level) also determines access to parameters.
Note:
P0010 = 1
The inverter can be commissioned very quickly and easily by setting P0010 = 1. After that only the
important parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be
entered one after the other. The end of quick commissioning and the start of internal calculation
will be done by setting P3900
= 1 - 3. Afterward parameter P0010 and P3900 will be reset to zero automatically.
P0010 = 2
For service purposes only.
P0010 = 29
To transfer a parameter file via PC tool (e.g.: DriveMonitor, STARTER) parameter P0010 will be set
to 29 by the PC tool. When download has been finished PC tool resets parameter P0010 to zero.
P0010 = 30
When resetting the parameters of inverter P0010 must be set to 30. Resetting of the parameters will
be started by setting parameter P0970 = 1. The inverter will automatically reset all its parameters
to their default settings. This can prove beneficial if you experience problems during parameter
setup and wish to start again. Duration of factory setting will take about 60 s.