Page 350 - Electronic Mechanic - TP - Volume - 2
P. 350
ELECTRONICS MECHANIC - CITS
r0002 Drive state Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays actual drive state.
Possible Settings:
0 Commissioning mode (P0010 != 0)
1 Drive ready
2 Drive fault active
3 Drive starting (DC-link precharging)
4 Drive running
5 Stopping (ramping down)
Dependency:
State 3 visible only while precharging DC link, and when externally powered communications board
is fitted.
P0003 User access level Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 1
P-Group: ALWAYS Active: first confirm QuickComm.: No Max: 4
Defines user access level to parameter sets. The default setting (standard) is sufficient for most
simple applications.
Possible Settings:
0 User defined parameter list - see P0013 for details on use
1 Standard: Allows access into most frequently used parameters.
2 Extended: Allows extended access e.g. to inverter I/O functions.
3 Expert: For expert use only.
4 Service: Only for use by authorized service personal - password protected.
P0004 Parameter filter Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 0
P-Group: ALWAYS Active: first confirm QuickComm: No Max: 22
Filters available parameters according to functionality to enable a more focussed approach to
commissioning.
Possible Settings:
0 All parameters
2 Inverter
3 Motor
7 Commands, binary I/O
8 ADC and DAC
10 Setpoint channel / RFG
12 Drive features
13 Motor control
20 Communication
21 Alarms / warnings / monitoring
22 Technology controller (e.g. PID)
Example:
P0004 = 22 specifies that only PID parameters will be visible.
333