            r0002     Drive state                                                          Min:   -
                                                    Datatype: U16      Unit: -             Def:   -
                      P-Group: COMMANDS                                                    Max:   -
                      Displays actual drive state.
                      Possible Settings:
                      0  Commissioning mode (P0010 != 0)
                      1  Drive ready
                      2  Drive fault active
                      3  Drive starting (DC-link precharging)
                      4  Drive running
                      5  Stopping (ramping down)
                      Dependency:
                      State 3 visible only while precharging DC link, and when externally powered communications board
                      is fitted.
            P0003     User access level                                                    Min:   0
                      CStat:  CUT                   Datatype: U16      Unit: -             Def:   1
                      P-Group: ALWAYS               Active: first confirm  QuickComm.: No  Max:   4
                      Defines user access level to parameter sets. The default setting (standard) is sufficient for most
                      simple applications.
                      Possible Settings:
                      0  User defined parameter list - see P0013 for details on use
                      1  Standard: Allows access into most frequently used parameters.
                      2  Extended: Allows extended access e.g. to inverter I/O functions.
                      3  Expert: For expert use only.
                      4  Service: Only for use by authorized service personal - password protected.
            P0004     Parameter filter                                                     Min:   0
                      CStat:  CUT                   Datatype: U16      Unit: -             Def:   0
                      P-Group: ALWAYS               Active: first confirm  QuickComm: No   Max:   22
                      Filters available parameters according to functionality to enable a more focussed approach to
                      commissioning.
                      Possible Settings:
                      0  All parameters
                      2  Inverter
                      3  Motor
                      7  Commands, binary I/O
                      8  ADC and DAC
                      10 Setpoint channel / RFG
                      12 Drive features
                      13 Motor control
                      20 Communication
                      21 Alarms / warnings / monitoring
                      22 Technology controller (e.g. PID)
                      Example:
                      P0004 = 22 specifies that only PID parameters will be visible.