P0011 Lock for user defined parameter Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 0
P-Group: FUNC Active: first confirm QuickComm.: No Max: 65535
Details: See parameter P0013 (user defined parameter)
P0012 Key for user defined parameter Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 0
P-Group: FUNC Active: first confirm QuickComm: No Max: 65535
Details: See parameter P0013 (user defined parameter).
P0013 User defined parameter Min: 0
[20] CStat: CUT Datatype: U16 Unit: - Def: 0
P-Group: FUNC Active: first confirm QuickComm.: No Max: 65535
Defines a limited set of parameters to which the end user will have access. Instructions for use:
1 Set P0003 = 3 (expert user)
2 Go to P0013 indices 0 to 16 (user list)
3 Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list. The
following values are fixed and cannot be changed:
- P0013 index 19 = 12 (key for user defined parameter)
- P0013 index 18 = 10 (commissioning parameter filter)
- P0013 index 17 = 3 (user access level)
4 Set P0003 = 0 to activate the user defined parameter.
Index:
P0013[0] : 1st user parameter P0013[1] : 2nd user parameter P0013[2] : 3rd user parameter
P0013[3] : 4th user parameter P0013[4] : 5th user parameter P0013[5] : 6th user parameter
P0013[6] : 7th user parameter P0013[7] : 8th user parameter P0013[8] : 9th user parameter
P0013[9] : 10th user parameter P0013[10] : 11th user parameter P0013[11] : 12th user parameter
P0013[12] : 13th user parameter P0013[13] : 14th user parameter P0013[14] : 15th user parameter
P0013[15] : 16th user parameter P0013[16] : 17th user parameter P0013[17] : 18th user parameter
P0013[18] : 19th user parameter P0013[19] : 20th user parameter
Dependency:
First, set P0011 (“lock”) to a different value than P0012 (“key”) to prevent changes to user-defined
parameter. Then, set P0003 to 0 to activate the user-defined list.
When locked and the user-defined parameter is activated, the only way to exit the user-defined
parameter (and view other parameters) is to set P0012 (“key”) to the value in P0011 (“lock”).
P0014 [3] Store mode Min: 0
CStat: UT Datatype: U16 Unit: - Def: 0
P-Group: - Active: first confirm QuickComm: No Max: 1
Sets the store mode for parameters (“volatile” (RAM) or “nonvolatile” (EEPROM)).
Possible Settings:
0 Volatile (RAM)
1 Nonvolatile (EEPROM)
Index:
P0014[0] : Serial interface COM link P0014[1] : Serial interface BOP link P0014[2] : PROFIBUS /